Guardrail attached to low fill culverts

Question
State OH
Description Text In Research Report No. TRP-03-278-13 - Post Weld and Epoxy Anchorage Variations for W-beam Guardrail Attached to Low-Fill Culverts, the results conclude that both ASTM A36 and Grade 50 steel post and base plates are expected to perform similarly.  The design Ohio uses is slightly different (see attached).  Would you expect this design to also perform similarly regardless of which of these two steels are used?

Thanks!
Keywords
  • Guardrail
Other Keywords none
Date August 14, 2018
Attachment low fill post.JPG


Response
Response
There are two MASH TL-3 crashworthy, top-mounted, strong-post, W-beam guardrail systems for use on low-fill culverts.  The report you referenced herein evaluated variations of a system developed at MwRSF.  This system incorporated a 1/2" thick base plate that is intended to yield and deform during loading.  this plastic deformation in the plate absorbs energy and limits the resistance forces of the posts. The second guardrail on culvert system was developed at TTI and incorporated a 7/8" thick base plate, which remains rigid during impacts.  Thus, the forces from the posts are higher. Both systems have been crash tested, so either can be used for treatments on low-fill culverts.

The drawings you attached appear to be utilizing the details from the TTI system.  The upper right base plate in the attachment has the same thickness, hole dimensions, and offset from the headwall as the TTI base plate.  Since the as-tested system used A36 steel and didn't experience deformations to the plate, the same result would be expected for a plate made from stronger, grade 50 steel.  A copy of the TTI report on this system is attached. 

The base plate detail shown in the upper left of your detail incorporates a wider design with lateral slots spaced 11" apart instead of 9". Also, this plate is thinner that the original plate (3/4" vs. 7/8").  The combination of a wider anchorage spacing and a thinner plate may alter the performance of this post-and-plate assembly.  As such, further analysis may be required to evaluate this baseplate design to MASH criteria.
Date August 14, 2018
Attachment 405160-23-2-box-culvert-rev2.pdf


Contact Us:
130 Whittier Research Center
2200 Vine Street
Lincoln, NE 68583-0853
(402) 472-0965
Email: mwrsf@unl.edu
Disclaimer:
The information contained on the Midwest Roadside Safety Facility (MwRSF) website is subject to change without prior notice. The University of Nebraska and the MwRSF is not responsible or liable, directly or indirectly, for any damage or loss caused or alleged to be caused by or in connection with the use or misuse of or reliance upon any such content, goods, or services available on this site.